- SG500MX/SG630MX
- 【Brief】:
Sales Area Asia Pacific Europe and the Middle East India and Sri Lanka Japan
High Yield
- Efficient three-level topology, max. efficiency up to 99 %
- Long-term overload at 1.1 Pn
- Full power operation without derating at 55 ℃
Easy O&M
- Integrated zone current monitoring function for fast trouble shooting
- Modular design and front service, easy for maintenance
Saved Investment
- Max. DC/AC ratio up to 1.3
- Integrated SVG function
Grid Support
- Compliance with standards: CE, IEC 62109, IEC 61727, IEC 62116
- Low/High voltage ride through (L/HVRT)
- Active & reactive power control and power ramp rate control
- 【Series】:Central Inverter
- Description
Technical Data
Input (DC) SG500MX SG630MX Max. PV input voltage 1000 V Min. PV input voltage / Startup input voltage 460 V / 500 V 520 V / 540 V MPP voltage range for nominal power 460 – 850 V 520 – 850 V No. of independent MPP inputs 1 No. of DC inputs 6 – 10 Max. PV input current 1220 A 1356 A Max. DC short-circuit current 1460 A 1695 A Output (AC) Nominal AC power (at 55 ˚C) 500 kW 630 kW Max. AC output at PF=1 (at 50 ˚C) 550 kVA 693 kVA Max. AC apparent power (at 50 ˚C) 550 kVA 693 kVA Max. AC output current 1008 A 1111 A Nominal AC voltage 315 V 360 V AC voltage range 252 – 362 V 288 – 414 V Nominal grid frequency / Grid frequency range 50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz THD < 3 % (at nominal power) DC current injection < 0.5 % In Power factor at nominal power / Adjustable power factor > 0.99 / 0.8 leading – 0.8 lagging Feed-in phases / Connection phases 3 / 3 Efficiency Max. efficiency / Euro. efficiency 99.0 % / 98.7 % Protection DC reverse connection protection Yes DC input protection Circuit breaker AC output protection Circuit breaker Overvoltage protection DC Type II / AC Type II Grid monitoring / Ground fault monitoring Yes / Yes Insulation monitoring Yes Overheat protection Yes Anti-PID function Optional General Data Dimensions (W*H*D) 1005*1915*835 mm Weight 800 kg Isolation method Transformerless Degree of protection IP21 Night power consumption < 20 W Operating ambient temperature range -30 to 65 ℃ (> 55 ℃ derating) Allowable relative humidity range (non-condensing) 0 – 95 % Cooling method Temperature controlled forced air cooling Max. operating altitude 4500 m (> 3500 m derating) Display Touch screen Communication RS485 / Modbus, Ethernet Compliance CEA, IEC 62109, IEC 61727, IEC 62116, IEC 60068, IEC 61683, CE Grid support SVG function, LVRT, HVRT, active & reactive power control and power ramp rate control Type designation SG500MX-10 SG630MX-10
Pre:SG1000/SG1250